LK 941 EasyMix

LK 941 EasyMix is a series of valve actuators. Depending on model the actuator can be operated by a controller with a 3-point SPDT output or a proportional 0-10 V / 4-20 mA output. The angle of rotation is elec...

LK 941 EasyMix

Variants

LK 941

LK 941 3 variants

Article Connection Voltage Torque Operation time A mm B mm C mm Weight (kg) Dimensional sketch Item List
066129 1 m cable 230 VAC 15 Nm 73 s 92.5 125 78 0.6
066132 1 m cable 230 VAC 15 Nm 147 s 92.5 125 78 0.6
066133 1 m cable. 0 - 10 VDC 24 VDC/AC 15 Nm 73 s 92.5 125 78 0.6

066129

Connection 1 m cable
Voltage 230 VAC
Torque 15 Nm
Operation time 73 s
A mm 92.5
B mm 125
C mm 78
Weight (kg) 0.6
Dimensional sketch
Item list

066132

Connection 1 m cable
Voltage 230 VAC
Torque 15 Nm
Operation time 147 s
A mm 92.5
B mm 125
C mm 78
Weight (kg) 0.6
Dimensional sketch
Item list

066133

Connection 1 m cable. 0 - 10 VDC
Voltage 24 VDC/AC
Torque 15 Nm
Operation time 73 s
A mm 92.5
B mm 125
C mm 78
Weight (kg) 0.6
Dimensional sketch
Item list

Detailed Information

Description

LK 941 EasyMix is a series of valve actuators. Depending on model the actuator can be operated by a controller with a 3-point SPDT output or a proportional 0-10 V / 4-20 mA output. The angle of rotation is electrically limited to 90°.

The actuator can be mounted in any position except below the valve. The actuator is mounted directly onto the valve spindle with a screw. An anti-rotation bolt keeps the actuator in position. When needed, the actuator can be put into manual mode by pressing and turning the button on the housing cover 90° to disengage the gears. The actuator can now be put in any position by turning the handle on the front. The position is indicated on the reversible scale.

LK 941 EasyMix fits most mixing valves on the market.

Technical Data

Voltage: 230 VAC 50 Hz
24 VAC 50 Hz
Power consumption: 6 VA
Angle of rotation: 90° electically limited
Torque: 15 Nm
Operation time: 73 s/147 s
Ambient temperature: Min. 0 °C/Max. 55 °C
Position indication: Reversible scale
Direction of operation: Selectable
Manual override: Disengagement of gears
Protection type: IP 44
Protection class: II
Electrical connection: Cable 1 m
Signal connector: 3-point SPDT
0-10 VDC/4-20 mA