LK Armatur Our websites English
Close

Our websites

RP Expansion Vessel

RP Expansion Vessel

Expansion vessel for heating, recovery and cooling systems.

RP Expansion Vessel

Variants

RP

RP 4 variants

Manufacturing standards: Expansion vessels manufactured in accordance with the European Directive PED 97/23 and the Swedish Pressure Vessels Directive AFS 1999: 4.

Article Dim. A mm Weight (kg) Dimensional sketch Item List
552 33 18 6 liter 100 4.4
552 33 19 8 liter 113 4.5
552 33 20 10 liter 128 4.8
552 33 21 12 liter 146 5.0

552 33 18

Dim. 6 liter
A mm 100
Weight (kg) 4.4
Dimensional sketch
Item list

552 33 19

Dim. 8 liter
A mm 113
Weight (kg) 4.5
Dimensional sketch
Item list

552 33 20

Dim. 10 liter
A mm 128
Weight (kg) 4.8
Dimensional sketch
Item list

552 33 21

Dim. 12 liter
A mm 146
Weight (kg) 5.0
Dimensional sketch
Item list

Detailed Information

Description

Expansion vessel for heating, recovery and cooling systems.

Expansion vessels must be installed according to instructions in VVA 93. The expansion vessel is inspected visually prior to installation. When installing with a system, the pre-pressure must be adjusted so that it matches the static pressure prevailing at the tank’s connection point. The adjustment takes place without the influence of system pressure (depressurised on the system side).

The expansion vessel does not require maintenance. Air valve must be provided with protective covering.

Technical Data

Max. working pressure: 3.0 bar
Working temperature: Min. –10 °C / Max. 70 °C
Maximum instantaneous temperature: 110 °C
Media 1: Water - Glycol mixture max. 50%
Other data: Material, vessel Closed expansion vessel in steel.
Material, internal membrane SBR rubber
Pre-charge of the vessels 0.5 bar. Other pre-charge on request.

Questions & Answers

I have an RP 12-litre expansion vessel with the port on the long side but I can’t find this product on your website.

We do have that product, it is article no. 064010

Which expansion vessel should I buy?

If your expansion vessel connection is located on the long side, you should choose expansion vessel article number: 064010. If your expansion vessel connection is located on the short side, you should choose expansion vessel article number: 5523321